Setting Procedure
The following example uses the LED operator as frequency reference and run
command source (LOCAL mode).
1.
Turn on the power to the drive.
2.
Set the frequencies listed below to the specified parameters:
1. d1-01 = 5 Hz: Step 1
2. d1-02 = 20 Hz: Step 2
3. d1-03 = 50 Hz: Step 3
4. d1-04 = 60 Hz: Step 4
3.
Press the
key until the Top Screen appears.
4.
turns on.
5.
Press
to select LOCAL. The LO/RE light will turn on.
6.
Press
to run the motor at 5 Hz. The RUN light will turn
RUN
on.
7.
With SW1closed, the drive runs the motor at Multi-Step Speed 2
(20 Hz).
8.
With SW1 open and SW2 closed, the drive runs the motor at
Multi-Step 3 (50 Hz).
9.
With both SW1 and SW2 closed, the drive runs the motor at
Multi-Step 4 (60 Hz).
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Step
<1>
<2>
4.5 Test Run
Display/Result
STOP
STOP
4
179