5.7 Operator Programming Errors
LED Operator Display
Frequency reference is assigned to an option card
(b1-01 = 3) that is not connected to the drive.
The run command is assigned to an option card
(b1-02 = 3) that is not connected to the drive.
Frequency reference is assigned to the pulse train input
(b1-01 = 4), but terminal RP is not set for pulse train input
(H6-01 is greater than 0).
LED Operator Display
H3-02 and H3-10 are set to the same value.
The following contradictory settings have been made at
the same time:
H3-02 or H3-10 = B (PID Feedback)
H6-01 (Pulse Train Input) = 1 (PID Feedback)
The following contradictory settings have been made at
the same time:
H3-02 or H3-10 = C (PID Target Value)
H6-01 = 2 (pulse train input sets the PID target value)
The following contradictory settings have been made at
the same time:
H3-02 or H3-10 = C (PID Target Value)
b5-18 = 1 (enables b5-19 as the target PID value)
The following contradictory settings have been made at
the same time:
H6-01 or H3-10 = C (PID Target Value)
b5-18 = 1 (enables b5-19 as the target PID value)
LED Operator Display
238
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
oPE05
Cause
oPE07
Cause
oPE08
Error Name
Run Command Selection Error
The run command selection parameter b1-02 is set to 3
but no option board is installed.
Possible Solutions
Reconnect the option card to the drive.
Reconnect the option card to the drive.
Set H6-01 to "0".
Error Name
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function
analog inputs H3-02 through to H3-10 and PID functions
conflict.
Possible Solutions
Change the settings to H3-02 and H3-10 so that functions
no longer conflict. Note: Both 0 (primary analog
frequency reference) and F (Not Used) can be set to
H3-02 and H3-10 at the same time.
Disable one of the PID selections.
Disable one of the PID selections.
Disable one of the PID selections.
Disable one of the PID selections.
Error Name
Parameter Selection Error
A function has been set that cannot be used in the motor
control method selected.