Set one or two digital input terminals between S1 and S7 for FJOG and RJOG
(H1-01 to H1-07 = "12" and "13").
No run command is required for JOG operation.
The JOG operation has the highest priority (i.e., other frequency references are
disregarded).
Jog Operation Parameters
No.
Name
Jog Frequency
d1-17
Reference
Selections for Digital Input Terminals S1 to S7 (H1-01 to H1-07)
Setting
12
FJOG Command (ON: rotates forward at the Jog frequency set to d1-17)
13
RJOG Command (ON: rotates in reverse at the Jog frequency set to d1-17)
Connection Example for the Jog Function
In this example, H1-07 = 12 and d1-17 = 6.0 Hz.
Figure 4.29
Three-Phase 200 Vac
(400 Vac)
Figure 4.29 Jog Command from External Terminals
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Description
Frequency reference when: "Jog Frequency
Reference" is selected via multi-function input
terminals. "Jog Frequency Reference" has priority
over "Multi-Step Speed Reference 1 to 16."
Parameter d1-17 is also the reference for the JOG
key on the digital operator, and the multi-function
inputs "Forward Jog" and "Reverse Jog."
R/L1
S/L2
T/L3
S7 (FJ0G)
SC
Setting
Range
0.00 to
400.00
Name
Drive
U/T1
V/T2
W/T3
4.5 Test Run
Default
Page
Setting
6.00 Hz
351
Page
M
175
4