Advertisement

No.
Name
Heatsink Cooling Fan
L8-10
Operation Selection
Heatsink Cooling Fan
L8-11
Operation Delay
Time
Ambient Temperature
L8-12
Setting
OL2 Characteristics
L8-15
Selection at Low
Speeds
L8-18 Soft CLA Selection
Frequency Reduction
L8-19
Rate during OH
Pre-Alarm
Current Unbalance
L8-29
Detection (LF2)
Side-by-Side
L8-35
Selection
Carrier Frequency
L8-38
Reduction
Current Alarm
L8-41
Selection
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Description
Controls the heatsink cooling fan operation.
0: Fan On-Run Mode - Fan will operate only
when the drive is running and for L8-11
seconds after RUN is removed.
1: Fan always on - Cooling fan operates
whenever the drive is powered up.
This parameter sets the delay time for the
cooling fan to shut off after the run command
is removed when L8-10 = 0.
Adjust the drive overload (OL2) protection
level when the drive is installed in an
environment that exceeds its ambient
temperature rating.
Assists in protecting the output transistors from
overheating when output current is high and
output frequency is low (6Hz and less).
0: Disabled - L8-16 and L8-17 are disabled.
1: Enabled - L8-16 and L8-17 are enabled.
Enables and disables the software current limit
function. This parameter does not typically
require adjustment. Consult the factory before
disabling.
0: Disabled
1: Enabled
Specifies the frequency reference derate when
L8-03 = 4.
Issues a stop command when the output current
is unbalanced as a result of output phase loss.
0: Disabled
1: Enabled
0: Disabled (standard installation)
1: Side-by-Side installation
2: NEMA Type 1
Provides protection to the IGBTs by reducing
the carrier frequency at low speeds.
0: Disabled
1: Enabled
Configures an alarm when the relative output
current rises above 150%.
0: Alarm disabled.
1: Alarm enabled (alarm is output).
B.2 Parameter Table
Control
Mode
Range Def.
Addr.
O
V/
P
Hex
L
f
M
V
0,1
0
A A A 4B6
0 to 300 60 s A A A 4B7
40
40 to 60
A A A 4B8
°C
0,1
1
A A A 4BB
1
A A − 4BE
0,1
<1>
0.1 to
0.8 A A A 4BF
1.0
− − A 4DF
0 to 1
1
Α Α A 4ECH —
0 to 2
0
0,1
0
A A A 4EF
0,1
0
A A A 4F2
Pg.
B
395