YASKAWA V1000 Series Installation & Start-Up Manual page 375

Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

H2-
Function
Setting
12
Timer Output
13
Fref/Fout Agree 2
14
Fref/Fset Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
Torque Detection 1
17
(N.C.)
Torque Detection 2
18
(N.O.)
Torque Detection 2
19
(N.C.)
1A
Reverse Direction
1B
Baseblock 2
1C
Motor 2 Selection
1E
Restart Enabled
Overload OL1 (OL1
1F
Alarm)
20
OH Pre alarm
Mechanical Weakening
22
(N.O.)
30
During Torque Limit
During Frequency
37
Output
38
Drive Enable
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
H2 Multi-Function Digital Output Settings
Output for independent timer, controlled by b4-01 and b4-02.
Used in conjunction with the digital input (H1-
function").
Closed: When drive output frequency equals the frequency
reference +/- L4-04.
Closed: When the drive output frequency and the frequency
reference are both equal to the value in L4-03 (plus or minus L4-
04).
Closed: When the drive output frequency is less than or equal to
the value in L4-03 with the hysteresis determined by L4-04.
Closed: When the output frequency is greater than or equal to the
value in L4-03 with the hysteresis determined by L4-04.
Open: When the output current/torque exceeds the value set in
parameter L6-02 for more time than is set in parameter L6-03.
Closed: When the output current/torque exceeds the value set in
parameter L6-05 for more time than is set in parameter L6-06.
Open: Output current/torque exceeds the value set in parameter
L6-05 for more time than is set in parameter L6-06.
Closed: Drive is running in the reverse direction.
Open: There is no voltage output.
Closed: Motor 2 is selected via one of the multi-function inputs
(H1-
= 16)
Closed: When the drive is performing an automatic restart.
Configure automatic restart with parameters L5-01 through L5-05.
Closed: OL1 is at 90% of its trip point or greater.
Closed: Heatsink temperature exceeds the value set to parameter
L8-02.
Closed: Mechanical Weakening detected.
Closed: When the torque limit has been reached.
Closed: Run command is present (except during baseblock and
during DC Injection Braking).
Open: Run command is been removed, or baseblock, DC Injection
Braking, or Initial Excitation is being performed.
Closed: Multi-function input closes (H1-
B.2 Parameter Table
Description
= 18 "timer
= 6A)
Control
Mode
Pg.
O
V/
P
L
f
M
V
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
B
O O O —
O O O —
O O O —
O O O —
− O − —
O O O —
O O O —
375