YASKAWA V1000 Series Installation & Start-Up Manual page 274

Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

6 . 2
In s p e c t i o n
Periodic Inspection
Inspection
Area
• Overall check of the main power circuit
and ground terminals
• Inspect equipment for discoloration from
overheating or deterioration.
• Inspect for damaged or deformed parts.
General
• Inspect for dirt, foreign particles, or dust
collection on components.
• Inspect wiring and connections for
Conductors and
discoloration, damage, or heat stress.
Wiring
• Inspect wire insulation and shielding for
wear.
• Inspect terminals for stripped, damaged,
Terminals
or loose connections.
• Check for tightness.
• Inspect contactors and relays for
Relays and
excessive noise during operation.
Contactors
• Inspect coils for signs of overheating
such as melted or cracked insulation.
Braking
• Inspect for discoloration of heat stress on
Resistors
or around resistors.
• Inspect for leakage, discoloration, or
Electrolytic
cracks.
(bus) Capacitors
• Inspect the relief valve for swelling,
rupture, or leakage.
Diodes and
• Inspect for accumulation of dust or other
IGBTs
foreign particles on components.
274
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Table 6.2 Periodic Inspection Checklist
Inspection Points
Main Circuit Periodic Inspection
Corrective Action
Take appropriate actions
(e.g., tightening loose connections).
• Replace damaged components as
required.
• The drive has few serviceable parts
and may require complete drive
replacement.
• Inspect enclosure door seal if present.
Replace components if cleaning is not
possible.
• Use dry air to clear away foreign
matter. Use a pressure of
39.2 ξ 10
4
to 58.8 x 10
(4 - 6 kg •cm
2
).
• Repair or replace damaged wiring.
• Tighten loose screws and replace
damaged screws or terminals.
• Check coil voltage for over or under
voltage conditions.
• Replace damaged removable relays
contactors or circuit board.
• Minor discoloration may be
acceptable.
• If discoloration exists check for loose
connections.
• The drive has few serviceable parts
and may require complete drive
replacement.
• Use dry air to clear away foreign
matter.
• Use a pressure of
39.2 ξ 10
to 58.8 ξ 10
4
(4 - 6 kg •cm
2
).
Checked
4
Pa
4
Pa

Hide quick links: