4.6 Basic Drive Setup Adjustments

Digital Outputs H2-01 to H2-03

Parameters H2-01, H2-02 and H2-03 assign functions to digital output terminals MA, MB,
MC, P1, and P2. Set these parameters as required by the application. Default values are
listed below.
NOTICE: Do not assign a function that repeats ON/OFF frequently to terminals MA and MB. Failure to
comply will reduce the relay contact lifetime. The expected number of relay contact switching times is
normally 200,000 times (current 1 A, resistance load).
No.
H2-01

Terminal MA, MB and MC Function Selection (relay)

H2-02
Terminal P1 Function Selection (open-collector)
H2-03
Terminal P2 Function Selection (open-collector)
Note: The setting range for H2-01 through H2-03 is 0 to 14D.
more information.
Figure 4.25

Analog Outputs: H4-01 to H4-03

Group U parameters can be used to observe the drive status (operating conditions) through
the LED operator. Analog outputs corresponding to these monitors can be obtained on
analog output terminal AM or Fm when programmed with parameter group H4. Some
Group U monitors are not available as analog outputs.
144
Parameter Name
Multi-Function Contact Outputs
250 Vac, 10 mA - 1 A
30 Vdc, 10 mA - 1 A
(standard default setting)
Multi-Function Open-collector Outputs
48 Vdc, 50 mA or less
(standard default setting)
Figure 4.25 Digital Output Connection Diagram
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Refer to Parameter List on page 305
Fault
MA
MB
Fault
MC
(Open-collector 1)
During Run
P1
(Open-collector 1)
Speed Agree
P2
Open-collector Common
PC
Default
E: Fault
0: During Run
2: Speed Agree 1
for