H1-
Function
Setting
1B
Program Lockout
1E
Reference Sample Hold
20 to
External Fault (user selection
2F
possible)
30
PID Integral Reset
31
PID Integral Hold
32
Multi-Step Speed Reference 4
34
PID Soft Starter
35
PID Input Switch
Forward Run Command
40
(2-wire sequence)
Reverse Run Command
41
(2-wire sequence)
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
H1 Multi-Function Digital Input Selections
Open: Only the frequency reference monitor (U1-01)
may be saved.
Closed: Parameters may be edited and saved.
Closed: Samples the analog frequency reference and
operates the drive at that speed.
20: N.O., Always Detected, Ramp To Stop
21: N.C., Always Detected, Ramp To Stop
22: N.O., During Run, Ramp To Stop
23: N.C., During Run, Ramp To Stop
24: N.O., Always Detected, Coast To Stop
25: N.C., Always Detected, Coast To Stop
26: N.O., During Run, Coast To Stop
27: N.C., During Run, Coast To Stop
28: N.O., Always Detected, Fast-stop
29: N.C., Always Detected, Fast-stop
2A: N.O., During Run, Fast-stop
2B: N.C., During Run, Fast-stop
2C: N.O., Always Detected, Alarm Only (continue
running)
2D: N.C., Always Detected, Alarm Only (continue
running)
2E: N.O., During Run, Alarm Only (continue running)
2F: N.C., During Run, Alarm Only (continue running)
Closed: Resets the PID control integral value.
A stop command was entered during PID control or PID
was reset while the drive was stopped.
Closed: Maintains the current level of the PID control
integral.
The values set to d1-01 through d1-16 can be selected
using a combination of multi-step speed reference 1
through 4.
Closed: Disregards b5-17.
Closed: Reverses the PID fault signal (1 to -1 or -1 to 1) O O O —
Open: Stop
Closed: Forward run
Note: Settings 42 and 43 cannot be utilized at the same
time.
Open: Stop
Closed: Reverse run
Determines direction only. Simply switching this signal
on or off does not issue a run command.
Settings 42 and 43 cannot be used at the same time.
B.2 Parameter Table
Description
Control
Mode
Pg.
V/
O
P
f
LV
M
O O O —
O O O —
O O O —
O O O —
B
O O O —
O O O —
O O O —
O O O —
O O O —