YASKAWA V1000 Series Installation & Start-Up Manual page 316

Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

A.2 Power Specifications
3. The carrier frequency default setting is 2 kHz for all ND models.
4. HD ratings have an overload of 150% for 1 minute. ND ratings have an overload of 120%
for 1 minute.
specifications.
Input
Drive
Phase
Duty
ND
Three-
Phase
HD
Note: 1. The Motor Capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of
the drive output amps should be equal to or greater than the motor rated current.
2. Rated motor capacity is calculated with a rated output voltage of 440 V.
3. The carrier frequency default setting is 2 kHz for all ND Duty models.
4. HD ratings have an overload of 150% for 1 minute. ND Duty ratings have an overload of
120% for 1 minute.
5. In 400 V class drives, certain restrictions apply to the maximum output frequency as
dictated by the carrier frequency and drive capacity. Contact Yaskawa for more
information.
specifications.
316
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Refer to Common Drive Specifications on page 317
Table A.3 Power Specifications 400 V Class Models
Default
Model
Carrier
Number
(kHz)
CIMR-V
4A0001
4A0002
4A0004
2
4A0005
4A0007
4A0009
4A0011
4A0001
4A0002
4A0004
8
4A0005
4A0007
4A0009
4A0011
Refer to Common Drive Specifications on page 317
Motor
Motor
Capacity
Capacity
(kW)
(HP)
0.37
0.5
0.75
1.0
1.5
2.0
2.2
3.0
3.0
4.0
3.7
5.0
5.5
7.5
0.2
0.25
0.4
0.5
0.75
1.0
1.5
2.0
2.2
3.0
3.0
4.0
4.0
5.5
for other drive
Input
Output
Current A
Current A
(rms)
(rms)
1.2
1.2
2.1
2.1
4.3
4.1
5.9
5.4
8.1
6.9
9.4
8.8
14.0
11.1
1.2
1.2
1.8
1.8
3.2
3.4
4.4
4.8
6.0
5.5
8.2
7.2
10.4
9.2
for other drive