Digital Output: H2-01

Parameter H2-01 assigns functions to digital output terminals MA, MB, and MC. Set this
parameter as required by the application. Default value is listed below.
NOTICE: Do not assign a function that repeats ON/OFF frequently to terminals MA and MB. Failure to comply
will reduce the relay contact lifetime. The expected number of relay contact switching times is normally
200,000 times (current 1 A, resistance load).
No.
H2-01
Terminal MA, MB and MC Function Selection (relay)
Note:
The setting range for H2-01 is 0 to 13D.
u

Analog Outputs: H4-01 to H4-03

Group U parameters can be used to observe the drive status (operating conditions) through
the LED operator. Analog outputs corresponding to these monitors can be obtained on analog
output terminal AM when programmed with parameter group H4. Some Group U monitors
are not available as analog outputs.
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
Set motor no-load current at rated voltage and rated frequency.
Contact the motor manufacturer to get the no-load current. This information is
not usually written on the motor nameplate.
The default no-load current is for a Yaskawa 4-pole motor.
Sets the phase-to-phase motor resistance in ohms.
Parameter Name
Refer to Parameter List on page 209
Multi-Function Contact Outputs
250 Vac, 10 mA - 1 A
30 Vdc, 10 mA - 1 A
(standard default setting)
MA
MB
MC
Figure 4.17 Digital Output Connection Diagram
http://nicontrols.com
Setting Method
Fault
Fault
4.5 Basic Operation
Default
E: Fault
for more information.
105
4