Alarm
Alarm Name
Sub
Number
Code
4464
OVER BCD RANGE
4465
OVER BINARY RANGE
(PARITY CHECK)
4466
OFFLINE UNDEFINED
0
COMMAND (ARITH)
4467
USER COORD STEP
NOT ENOUGH
4468
ROBOT CALIBRATION
1
DATA ERROR
2
3
4
5
6
7
Meaning
Cause
Setting error
Setting error
An undefined command was
Software operation error
issued to the offline position-data
occurred
preparation section.
Setting error
The calibration between
Setting error
manipulators cannot be executed
for this model.
The master group and the slave
Software operation error
group are set to the same group.
occurred
Incorrect designation of the
Software operation error
control group for master group
occurred
Incorrect designation of the
Software operation error
control group for slave group
occurred
Incorrect designation of the
Software operation error
occupation control group for
occurred
calibration data
Incorrect designation of the
Software operation error
enabling control group for
occurred
calibration data
Among three points in the master-
Setting error
group's calibration data, two or
three points are on the same
point.
Remedy
(1)Check the following settings.
·Correct the BCD data so that it is within the limit.
(1)Check the following settings.
·Correct the binary data so that it is within the limit.
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Check the following settings.
·Correct the JOB that the number of steps will be three or more.
(1)Check the following settings.
·Do not use a coordinated motion with this manipulator.
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Check the following settings.
·Teach the data for calibration so that each point is different.