Alarm
Alarm Name
Sub
Number
Code
5
6
7
8
9
10
Meaning
Cause
The SD parameter is damaged.
Data error
Main CPU board failure
The CIO parameter is damaged.
Data error
Main CPU board failure
The FD parameter is damaged.
Data error
Main CPU board failure
The AP parameter is damaged.
Data error
Main CPU board failure
The RS parameter is damaged.
Data error
Main CPU board failure
The SE parameter is damaged.
Data error
Main CPU board failure
Remedy
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.