YASKAWA FS100 Maintenance Manual page 136

Hide thumbs Also See for FS100:
Table of Contents

Advertisement

Alarm
Alarm Name
Sub
Number
Code
20
21
22
23
24
25
26
1020
MotoPlus application load
1
error
2
3
4
Meaning
Cause
The SRDY signal did not turn ON
Servo control board failure
after the WRITE ENABLE
command was written. (EEPROM
WRITE ENABLE error)
The SRDY signal did not turn ON
Servo control board failure
after the WRITE PROTECT
command was written. (EEPROM
WRITE PROTECT error)
The SRDY signal did not turn ON
Servo control board failure
after the ERASE command was
written. (EEPROM ERASE error)
The SRDY signal did not turn ON
Servo control board failure
after the CLEAR command was
written. (EEPROM CLEAR error)
The SRDY signal did not turn ON
Servo control board failure
after data were written.
(EEPROM writing error)
The SRDY signal did not turn ON
Servo control board failure
after data were read.
(EEPROM reading error)
The written data were rejected at
Servo control board failure
verification.
(EEPROM verify error)
Num of the Application files is
Setting error
over the limit.
Insufficient memory space
Setting error
MotoPlus application folder
Setting error
cannot be found.
Memory size required by
Setting error
Application is over the limit
(2Mbyte).
Remedy
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
Set the number of application file "*.OUT" to be within the defined value. (Delete
unnecessary files from the MotoPlus menu of the maintenance mode.)
Memory to work MotoPlus application is insufficient under the combination of
current system configuration and its optional function. IIf the alarm occurs
again, save the CMOS.BIN in maintenance mode, and then contact your
YASKAWA representative about occurrence status (operating procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller and load the MotoPlus
application which was loaded to the previous controller.
Check that if the object file name is too long or inappropriate letters are used.