YASKAWA FS100 Maintenance Manual page 137

Hide thumbs Also See for FS100:
Table of Contents

Advertisement

Alarm
Alarm Name
Sub
Number
Code
5
6
7
8
9
10
11
12
13
1030
MEMORY ERROR
0
(PARAMETER FILE)
Meaning
Cause
Undefined symbols are included
Setting error
in the application.
Load failure (other)
Setting error
API library initialization failure
Setting error
User root task not included
Setting error
User root task generation failure
Setting error
RAM-Disk generation failure
Setting error
MotoPlus application process
Setting error
generation failure
application file "*.VXE" in the
Setting error
controller exceeded the specified
value
Failure to install the driver to
Setting error
communicate between MotoPlus
application and the system.
RCD, RCxG parameter error
Data error
Main CPU board failure
Remedy
Check that symbols such as undefined functions or constants, which are
provided from the system side, are included in the application program.
(1)Check the definition of static variable in the MotoPlus application program is
correct or not.
(2)Check the MotoPlus application programs so that they are set within the
specified values.
(3)Check that the object files are appropriately created.
Memory to work MotoPlus application is insufficient under the combination of
current system configuration and its optional function. If the alarm occurs again,
save the CMOS.BIN in maintenance mode, and then contact your YASKAWA
representative about occurrence status (operating procedure).
Confirm that mpUsRoot() is described in the application program.
Memory to work MotoPlus application is insufficient under the combination of
current system configuration and its optional function. IIf the alarm occurs
again, save the CMOS.BIN in maintenance mode, and then contact your
YASKAWA representative about occurrence status (operating procedure).
Memory to work MotoPlus application is insufficient under the combination of
current system configuration and its optional function. If the alarm occurs again,
save the CMOS.BIN in maintenance mode, and then contact your YASKAWA
representative about occurrence status (operating procedure).
Check that the object file is appropriately created.
Set the number of application file "*.VXE" to be within the defined value. (Delete
unnecessary files from the MotoPlus menu of the maintenance mode.)
Memory to work MotoPlus application is insufficient under the combination of
current system configuration and its optional function. If the alarm occurs again,
save the CMOS.BIN in maintenance mode, and then contact your YASKAWA
representative about occurrence status (operating procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate parameter file in
maintenance mode, and then load the parameter file saved in the external
memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
137 of 348