YASKAWA FS100 Maintenance Manual page 186

Hide thumbs Also See for FS100:
Table of Contents

Advertisement

Alarm
Alarm Name
Sub
Number
Code
2
3
4
5
100
101
Meaning
Cause
An error occurred in the creation
Software operation error
of transmission socket during the
occurred
UDP process of the Ethernet
function.
Main CPU board failure
Illegal data were received in the
Software operation error
UDP process of the Ethernet
occurred
function.
Main CPU board failure
Transmission error occurred in the
Software operation error
UDP process of the Ethernet
occurred
function.
Main CPU board failure
The SELECT operation was not
Software operation error
successfully completed in the
occurred
UDP process of the Ethernet
function.
Main CPU board failure
The re-initialization notification of
Software operation error
illegal data length was received in
occurred
the UDP process of the Ethernet
function.
Main CPU board failure
The re-initialization notification of
Software operation error
illegal data was received in the
occurred
UDP process of the Ethernet
function.
Main CPU board failure
Remedy
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.