YASKAWA FS100 Maintenance Manual page 172

Hide thumbs Also See for FS100:
Table of Contents

Advertisement

Alarm
Alarm Name
Sub
Number
Code
4039
MEMORY ERROR
(FORM CUT FILE)
4040
MEMORY ERROR
(SHOCK LEVEL FILE)
4042
MEMORY ERROR
(VISION FILE)
4043
MEMORY ERROR
(VISION CALIBRATION)
4046
MEMORY ERROR
(CONVEYOR CALIB
FILE)
Meaning
Cause
Main CPU board failure
Sub Code: File number
Data error
Main CPU board failure
Sub Code: File number
Data error
Main CPU board failure
Sub Code: Page number
Data error
Main CPU board failure
Sub Code: Page number
Data error
Main CPU board failure
Sub Code: File number
Data error
Main CPU board failure
Remedy
(1)Reset the alarm.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm.
(2)If the alarm occurs again, initialize the form cut file in maintenance mode,
and then load the form cut file saved in the external memory device.
(1)Reset the alarm.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm.
(2)If the alarm occurs again, initialize the shock level file in maintenance mode,
and then load the shock level file saved in the external memory device.
(1)Reset the alarm.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm.
(2)If the alarm occurs again, initialize the vision condition file in maintenance
mode, and then load the vision condition file saved in the external memory
device.
(1)Reset the alarm.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm.
(2)If the alarm occurs again, initialize the vision calibration file in maintenance
mode, and then load the vision calibration file saved in the external memory
device.
(1)Reset the alarm.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm.
(2)If the alarm occurs again, initialize the conveyor calibration file in
maintenance mode, and then load the conveyor calibration file saved in the
external memory device.
(1)Reset the alarm.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
172 of 348