YASKAWA FS100 Maintenance Manual page 133

Hide thumbs Also See for FS100:
Table of Contents

Advertisement

Alarm
Alarm Name
Sub
Number
Code
18
19
20
21
790
MEMORY BATTERY
WEAK
820
CNTR01R HARDWARE
ERROR
Meaning
Cause
The number of operation
Data error
instructions exceed the
permissible value.
Main CPU board failure
A syntax error was found in the
Data error
CNT instruction or TMR
instruction.
Main CPU board failure
A syntax error was found in the
Data error
JMP-LABEL instructions.
Main CPU board failure
The label of JMP destination does
Data error
not exist.
Main CPU board failure
Main CPU board battery is
Connection failure
weakening.
Connection failure
Sub Code: Option board. Number
CNTR01R board failure
× 100 factor
factor:
1 ROM ERR
2 RAM ERR
3 CPU ERR
4 SHARED MEMORY ERR
5 CNTR ASIC ERR
Remedy
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Confirm that the battery is appropriately connected to the main CPU board.
(1)Replace the battery in accordance with the instructions in FS100
MAINTENANCE MANUAL.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the CNTR01R board. Save the CMOS.BIN
before replacing the board to be safe.
133 of 348