Alarm
Alarm Name
Sub
Number
Code
92
99
4203
SYSTEM ERROR
-1
(POSITION DATA)
-3
-6
Meaning
Cause
A job data was destroyed.
Software operation error
occurred
A job data in the memory was
Software operation error
destroyed.
occurred
The memory area for position
Software operation error
data is lacking at the initialization
occurred
of the position data control
process.
Main CPU board failure
The number of axes for position
Software operation error
data is zero.
occurred
Main CPU board failure
Unused position data file is
Software operation error
destroyed.
occurred
Main CPU board failure
Remedy
(1)Reset the alarm.
(2)If the error occurs again, delete the job where the alarm occurred.
(3)If the error occurs again after the previous measures were executed,
initialize the job file in the maintenance mode, and then load the saved job file.
(4)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm.
(2)If the error occurs again, delete the job where the alarm occurred.
(3)If the error occurs again after the previous measures were executed,
initialize the job file in the maintenance mode, and then load the saved job file.
(4)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.