Alarm
Alarm Name
Sub
Number
Code
3090
4718
I/O MODULE 24V
POWER ERROR
4719
BINARY ETHERNET
1
CLIENT FUNC ERR
2
3
4
10
Meaning
Cause
In a file sever task, file close
Software operation error
error.
occurred
Sub Code: I/O Board slot(BIT)
Fuse failure
For example slot3 case:
(0000_0100), slot4
case:(0000_1000). If multiple
I/O boards detecting the error,
multiple bits are set. (Standard
shipping of FS100, An I/O
board is in slot3.)
Detect message library
Software operation error
initialize error.
occurred
Failed in the generation of the
Software operation error
file function task.
occurred
Failed in the generation of the
Software operation error
RC function task.
occurred
Detect I/F data error.
Software operation error
occurred
Detect undefined error.
Software operation error
occurred
Remedy
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
I/O board (LIO08R/09R) detected 24V power failure. Check the
following items.
(1) Check the fuse on the front panel of FS100, and replace it if it was
cut.
(2) Check the CN3 connecter and the cable of the I/O board.
(3) If the error occurs again, replace the LIO08R/09R board.
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your YASKAWA representative about
occurrence status (operating procedure).