YASKAWA FS100 Maintenance Manual page 184

Hide thumbs Also See for FS100:
Table of Contents

Advertisement

Alarm
Alarm Name
Sub
Number
Code
42
50
51
52
53
54
Meaning
Cause
Illegal e-mail data were received
Software operation error
in the FTP client task of the
occurred
Ethernet function.
Main CPU board failure
An error occurred in the data size
Software operation error
written to PCI of the Ethernet
occurred
function.
Main CPU board failure
An error occurred when the
Software operation error
request to write PCI data was
occurred
received in the Ethernet function.
Main CPU board failure
The request of the undefined
Software operation error
transmission was received in the
occurred
Ethernet function.
Main CPU board failure
An error occurred in the
Software operation error
transmission request of the
occurred
Ethernet function.
Main CPU board failure
The transmission request without
Software operation error
data was received in the Ethernet
occurred
function.
Main CPU board failure
Remedy
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller.
184 of 348

Advertisement

Table of Contents
loading

Table of Contents