YASKAWA FS100 Maintenance Manual page 191

Hide thumbs Also See for FS100:
Table of Contents

Advertisement

Alarm
Alarm Name
Sub
Number
Code
-10
-11
-12
-13
-16
Meaning
Cause
Main CPU board failure
An error occurred in job data
Software operation error
control system.
occurred
Main CPU board failure
An error occurred in sequence
Software operation error
number of the accessed job.
occurred
Main CPU board failure
An error occurred in step number
Software operation error
of the accessed job.
occurred
Main CPU board failure
A job specified at job search did
Software operation error
not exist in the memory.
occurred
Main CPU board failure
Unused handles were lacking
Software operation error
when an attempt was made to
occurred
open a job.
Main CPU board failure
Remedy
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
191 of 348