Alarm
Alarm Name
Sub
Number
Code
2
3
1651
FILE TRANSFER DATA
1
SIZE ERRORERROR
(SV)
2
1652
DB ON ERROR (SERVO)
1653
BASE BLOCK SIGNAL
ERROR
(SERVO)
Meaning
Cause
Main CPU board failure
An error occurred when the first
Servo control board failure
data was not received during on
the way data communication at
execution of motion command.
An error occurred when the first
Servo control board failure
data was not received during the
last data communication at
execution of motion command.
The data size for the file transfer
Servo control board failure
does not agree with the received
buffer size.
Buffer size over
Servo control board failure
Servo control board failure
Software operation error
occurred
Servo control board failure
Software operation error
occurred
Module failure (amplifier)
Remedy
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your YASKAWA representative about occurrence status (operating
procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace controller. Save the CMOS.BIN before
replace controller to be safe.