YASKAWA FS100 Maintenance Manual page 131

Hide thumbs Also See for FS100:
Table of Contents

Advertisement

Alarm
Alarm Name
Sub
Number
Code
6
7
8
9
10
11
Meaning
Cause
Unconnected relay exists.
Data error
Main CPU board failure
The STR instructions are
Data error
overused.
Main CPU board failure
The AND-STR instructions are
Data error
overused.
Main CPU board failure
A syntax error was found in the
Data error
CNT instruction.
Main CPU board failure
The head of the block starts with
Data error
an instruction other than the STR
instruction.
Main CPU board failure
Excessive machine codes
Data error
Main CPU board failure
Remedy
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, initialize the appropriate data in maintenance
mode, and then load the data saved in the external memory device.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
131 of 348