YASKAWA FS100 Maintenance Manual page 113

Hide thumbs Also See for FS100:
Table of Contents

Advertisement

Alarm
Alarm Name
Sub
Number
Code
50
51
60
COMMUNICATION
0
ERROR
(I/O MODULE)
1
Meaning
Cause
The system program of Servo
Software operation error
control board #1 is damaged.
occurred
Servo control board failure
The system program of Servo
Software operation error
control board #2 is damaged.
occurred
Servo control board failure
The IO module board connected
Software operation error
with 0th serial bus exists.
occurred
Main CPU board failure
An error was detected in
Setting error
communications with the I/O
module board connected with 1st
serial bus when the control power
turned ON.
Connection failure
Board failure
(I/O module)
Main CPU board failure
Remedy
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
1)Check the following settings.
·The rotary switch setting which specifies slot numbers of each I/O module
·I/O module settings in maintenance mode
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connecting or inserting state of the
following cables or connectors.
·IO module cable of the corresponding slot.
·Terminator
·24V power of the corresponding IO module.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the following board. Save the CMOS.BIN
before replace the board to be safe.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.