FAN to be replaced
STEP 6
Fasten the new FAN with the two screws.
STEP 7
Connect the PWR cables to the connector. This will starts the FAN.
STEP 8
Repeat the steps explained above again for the remaining FANs as needed.
When replacing two or three FANs while the system is in operation, if you attempt to replace multiple
Note:
FANs at a time, the chassis might be heated up. For this reason, when replacing multiple FANs, be sure
to replace them one by one.
7.2 Test Procedure After the Replacement
STEP 1
Check to see if the replaced FANs are operating normally.
•
All FANs are operating normally?
STEP 2
If any FAN is not operating, check the PWR cable of the FAN.
STEP 3
Attach the FAN cover again.
CHAPTER 2
・ ・ ・
・ ・ ・
・ ・ ・
・
・ ・ ・
・ ・ ・
・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・
・ ・ ・
・ ・ ・
・ ・
・ ・ ・
・ ・ ・
– 89 –
Operations of SV8500 Server