5-68 RLCM-EDC alarm clearing procedures
PM LCM
PM LCM
minor
minor
(end)
(continued)
25
26
27
28
297-8381-550 Standard 02.02 April 1999
The card list identifies the cards that have possible faults. Replace the cards
one at a time in the order listed from top to bottom.
If you
replaced a card on the list
did not replace a card on the list
For additional help, contact the next level of support.
Go to the Card Replacement Procedures to replace the first (or next) card on
the card list. After you replace the card, return to the step in this procedure
indicated in the following table.
If you
are clearing a PBsy alarm
are clearing drawer faults
are clearing all other alarms
The procedure is complete. If the system displays additional alarms, proceed
to the correct alarm clearing procedure.
Do
step 27
step 26
Do
step 15
step 20
step 23