Replacing an NT6X54 in LCM
At your current location
1
If you enter this procedure because of a loss of power in the LCM
controller (LTC+), check logutil. Check for PM181 log with
reason text:
DCC BIC Looparound
Proceed to step 2 if one of the following conditions applies:
another maintenance procedure directed you to this card replacement
procedure
you use the procedure to verify or accept cards
your maintenance support group directed you to this procedure
2
Obtain a replacement card. Make sure the replacement card has the same
product equipment code (PEC) and PEC suffix,as the card to remove.
If the Alarm Clearing Procedures directs you to this procedure, go to step 7. If
3
that procedure does not direct you to this procedure, proceed to step 4.
At the MAP terminal
4
To access the peripheral module (PM) level of the MAP terminal and post the
RLCM-EDC, type
>MAPCI;MTC;PM;POST LCM site cabinet lcm
and press the Enter key.
where
site
is the site name of the RLCM (alphanumeric)
cabinet
is the number of the RLCC cabinet
lcm
is the number of the LCM
Example of a MAP response:
LCM
REM1 00 0
Unit0: InSv Mtce
Unit1: InSv Mtce
Drwr:
01 23 45 67 89 01 23 45 67 89
.. SS .. .. .. .. .. .. .. ..
RLCM-EDC card replacement procedures 6-105
ATTENTION
. Go to step 7.
ISTb
Links OOS: Cside
11 11 11 11 11 RG: Uneq
DMS-100 Family Maintenance Manual ABSK007
NT6X54
in LCM