Nortel DMS-100 Series Maintenance Manual page 187

Remote line concentrating module with extended distance capability
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

9
To return the link to service, type
>RTS LINK link_no
and press the Enter key.
where
link_no
is the number of the P-side link busied in step 8
If
RTS PASSES
RTS FAILES
10
Determine if you must clear additional links
If the links that have defects
are cleared
are not cleared
11
To post the RMM, type
>POST RMM rmm_no
and press the Enter key.
where
rmm_no
is the number of the RMM associated with the link that has defects
12
To test the RMM, type
>TST
and press the Enter key.
If test
TST PASSED
TST FAILED, and the system
produces a card list
TST FAILED, and the system
does not produce a card list
RLCM-EDC alarm clearing procedures 5-73
Do
step 10
step 15
Do
step 11
step 8
Do
step 16
step 13
step 15
DMS-100 Family Maintenance Manual ABSK007
PM RMM
minor
(continued)