Nortel DMS-100 Series Maintenance Manual page 227

Remote line concentrating module with extended distance capability
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

Replacing an NT2X57
At your current location
1
Obtain a replacement card. Make sure the replacement card has the same
product equipment code (PEC), and PEC suffix.
At the MAP display
2
To access the TTP level of the MAP display and post the signal distribution
circuits on the card, type
>MAPCI;MTC;TRKS;TTP;POST P RMM rmm_no ckt_no
and press the Enter key.
where
rmm_no
is the number of the RMM shelf, the location of the card to remove.
ckt_no
is the number of the first circuit and the location of the NT2X57 card.
Example of a MAP response:
LAST CIRCUIT = 14
POST CKT IDLED
SHORT CLLI IS:
OK, CLLI POSTED
POST
13
DELQ
TTP 6–006
CKT TYPE
PM NO.
OG TESTEQ RMM 0 0
At the RMM shelf
3
WARNING
Static electricity damage
Wear a wrist strap connected to the wrist-strap
grounding point of a frame supervisory panel (FSP) to
handle circuit cards. The wrist strap protects the cards
against static electricity damage.
To replace the NT2X57 card, use the procedure "Replacing an NT2X57 card.
When the procedure is complete, return to this point.
RLCM-EDC card replacement procedures 6-39
1147
BUSY Q
COM LANG
OAUSD 0
DMS-100 Family Maintenance Manual ABSK007
NT2X57
in RMM
(continued)
DIG
STA S R DOT TE R
IDL