Nortel DMS-100 Series Maintenance Manual page 122

Remote line concentrating module with extended distance capability
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

5-8 RLCM-EDC alarm clearing procedures
PM LCM
critical
(continued)
14
PM Type: LCM
LCM REM1 02 0
ESA equipped: No, Intraswitching is Off
Loadname: LCMINV – REDC07AA
Unit0 Loads: Act– REDC07AB Stby– REDC07AA
Unit1 Loads: Act– REDC07AB Stby– REDC07AA
REX is ON; INCOMPLETE on SAT. 1995/10/28 at 01:35:19
Node Status: {MAN_BUSY, FALSE}
Unit 0 Status: {MAN_BUSY, FALSE}
Unit 1 Status: {MAN_BUSY, FALSE}
Site Flr RPos
REM1
Services : NEUTRAL
15
297-8381-550 Standard 02.02 April 1999
To query the LCM for correct loadfile names, type
>QUERYPM OOS
and press the Enter key.
Example of a MAP response
Int. No.: 9
Memory Size – Unit 0: 4M , Unit 1: 4M
Bay_id
01
K03
RLCM 02
If loadfile names
are valid
are invalid or corrupted
To return to service (RTS) the PM, type
>RTS PM
and press the Enter key.
If RTS
passes
fails
Status index: 7
Shf
Description
04
LCM
02 0
Do
step 15
step 22
Do
step 32
step 16
Node_No: 40
Slot
EqPEC