Nortel DMS-100 Series Maintenance Manual page 145

Remote line concentrating module with extended distance capability
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

18
Obtain a replacement fuse with the same voltage and amperage as the blown
fuse.
19
Use the following table to determine which drawer in the shelf below the fuse
panel is associated with the blown fuse.
Fuse number
01, 06, 11
02, 07, 12
03, 08, 13
04, 09, 14
05, 10, 15
20
CAUTION
Loss of service
Perform this procedure during periods of low traffic.
Pull out the line drawer you have just identified.
RLCM-EDC alarm clearing procedures 5-31
RLCC-EDC cabinet major
Drawer number
Array 0
0 (leftmost)
1
2
3
4
DMS-100 Family Maintenance Manual ABSK007
Ext FSP
(continued)
Drawer number
Array 1
5 (leftmost)
6
7
8
9