Nortel DMS-100 Series Maintenance Manual page 160

Remote line concentrating module with extended distance capability
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

5-46 RLCM-EDC alarm clearing procedures
Ext FSP
Ext FSP
RLCC-EDC cabinet major
RLCC-EDC cabinet major
At the RLCC-EDC cabinet
95
96
97
98
297-8381-550 Standard 02.02 April 1999
(continued)
(end)
Make a visual inspection of the FSP. Check circuit breakers CB5 and CB9.
If circuit breakers are
tripped
not tripped
Reset circuit breaker (CB8 or CB9) by moving the switch to the ON/OFF and
back to the ON position in quick succession. (The LED light should go OFF.)
If circuit breaker
trips again
remains ON (LED goes off)
For further assistance, contact the personnel responsible for the next level of
support.
You have successfully completed this procedure.
Do
step 96
step 98
Do
step 97
step 98