Nortel DMS-100 Series Maintenance Manual page 178

Remote line concentrating module with extended distance capability
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

5-64 RLCM-EDC alarm clearing procedures
PM LCM
minor
(continued)
13
14
15
16
297-8381-550 Standard 02.02 April 1999
To post the RMM that has faults, type
>POST RMM rmm_no
and press the Enter key.
where
rmm_no
is the number of the RMM identified in step12
To busy the RMM, type
>BSY
and press the Enter key.
To test the RMM, type
>TST
and press the Enter key.
If test
passed
failed, and the system produces a
card list
failed, but the system did not
produce a card list
To return to service the RMM, type
>RTS
and press the Enter key.
If RTS
passed
failed
Do
step 16
step 25
step 26
Do
step 28
step 26