Nortel DMS-100 Series Maintenance Manual page 121

Remote line concentrating module with extended distance capability
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

10
To return to service (RTS) the busied link, type
>RTS LINK link_no
and press the Enter key.
where
link_no
is the number of a P-side link tested in step 9
Note: Repeat this step for each link correctly tested.
If RTS
passes and no other links are system busy (SysB)
passes but other links are SysB
fails
11
To identify the RLCM-EDC that has faults, type
>DISP STATE SYSB LCM
and press the Enter key.
If response
does not indicate SysB LCMs
indicates SysB LCMs
12
To post the RLCM-EDC identified in step 11 with the alarm condition, type
>POST LCM SYSB
and press the Enter key.
13
To busy both LCM units of the RLCM-EDC, type
>BSY PM
and press the Enter key.
RLCM-EDC alarm clearing procedures 5-7
Do
step 32
step 12
DMS-100 Family Maintenance Manual ABSK007
PM LCM
critical
(continued)
Do
step 11
step 8
step 24