FF-SRT Series
APPLICATION EXAMPLE
DOOR PROTECTION USING SOLENOID KEY OPERATING SWITCH (MECHANICAL LATCH) AND FF-SRT TIME DELAY
MODULE
L1
(+)
Fuse
Sw2-21 Sw2-13
Key
Opening
Sw2-22 Sw2-14
Emergency
Stop
A1
A2
IMPROPER TIME DELAY USE
Always use time delay module connected to non safety related machine operation and use safety control modules as e-
stop, door, two-hand control to immediately stop dangerous motion.
Never use a time delay when the machine reaction time is not consistent in this case use a standstill monitor control
module
FF-SR05936.
The FF-SRT module time delay value must be selected or adjusted to be greater than the time necessary to stop the
hazardous machine motion for both regular and emergency stop conditions (includes power removal).
Failure to comply with these instructions could result in death or serious injury.
MODULE CONTACTS DAMAGE
Use arc suppressors across the coil of the safety relays K1, K2, K4, K5 and K6 to increase the life of the modules.
Failure to comply with these instructions will result in product damage.
The cable resistance between S11-S12 and S21-S22 of the FF-SRS5935 e-stop module must be less than 68 Ohms for
correct operation of the module.
6
Sw1-21 Sw1-13 Term4
Sol.
Sw1-22 Sw1-14 Term5
S
S
S
(+)
11
12
22
13
23
33
41
Honeywell
FF-SRS5935
Power
S1
K2
K3
S2
Internal
Switches
S
S
S21
(-)
33
34
PE
14
24
34
42
Restart
K1
K2
K4
K5
K6
K1
K5
K4
O
n
Motor
Off
Off
Motor
Motor
Lock
Door
K1
K2
Power
*
K4
K5
K6
Unlock
Door
K1
K2
PK 107019-01-EN FR26 GLO 398 Printed in Germany
PK 107019-01
ISSUE 1
L1
L2
L3
Fuse
K4
K2
K5
M
3
Ph.
A
1
2
1 (+
5
7
)
Honeywell
FF-SRTxx2xx
A2
(-)
16
28
K6
K1
K2
*
K6