Figure 4.6 : Connection of the protective equipment outputs
The following reversed connection is recommended for a better failure resistance :
+24Vdc
0.5A
OSSD1
1
20
19
+24V
(+
(-)
POWE
(+
(-)
FF-
13
14
OSSD
0V
Features
Type
Consumption
low level
high level
Protections
4.5.2 TEST output
TEST SEQUENCE AT POWER UP / SETTING ON DELIVERY
A test of the protective equipment is automatically done at start up to control the
connection of its outputs to the module terminals. For this reason, it is recommended to use
the same power supply source for the module and the protective equipment (or make sure
power is switched on simultaneously with the same switching device).
On delivery, the muting module provides a normally closed contact between terminals
28 and 29. All the above mentioned protective equipment need a normally closed contact
on their test input with the exception of the FF-SCAN, the FF-LS and the FF-SPS4 which
need a normally open contact.
The test output can be changed to a normally open contact.
If the test output is not used, the detection field of the protective equipment must be
interrupted 100 ms after power up, before restarting the module.
107004-15 EN FR26 ROW 0899 Printed in France
+24Vdc
0.5A
OSSD2
1
20
+24V
(+)
POWER
OSSD1
(+)
FF-SRM
13
0V
OSSD1 & OSSD2 inputs
voltage free and without reference potential
30 mA/24 Vdc
10 mA max.
19 mA min.
galvanic insulation: 500 Vdc, reversed polarity
19
(-)
(-)
14
53