FF-SPS4 Series Installation Manual
Figure 2-1 Perimeter Guarding System Safety Distance Diagram
IMPROPER FF-SPS4 SERIES APPLICATION
• A minimum of two beams are required to properly apply the FF-SPS4 Series safety
perimeter guarding devices.
• Entry into the protected area must be allowed only by interruption of the sensing beams.
Failure to comply with these instructions could result in death or serious injury.
Number of Beams
2
3
4
Sample Calculation
Country: USA
Application: Robotics
Protection: Perimeter Guarding
Formula: D
>V(t
S
− V = 63 in./sec.
− t
= 20 ms (FF-SPS4)
1
− t
= 200 ms (machine stop time; including response time of all interconnecting components,
2
such as relays, solenoids, brakes, etc.)
− C = 33.5 in. (USA)
− D
= 63 (0.020 + 0.200) + 33.5 in. = 47.36 in.
S
For application help: call 1-800-537-6945
Height Above Floor mm (in.)
400 (15.7)
900 (35.4)
300 (11.8)
700 (27.6)
1100 (43.3)
300 (11.8)
600 (23.6)
900 (35.4)
1200 (47.2)
+t
)+C
1
2
D
S
Honeywell • MICRO SWITCH Sensing and Control 15
Installation