MICRO SWITCH Maintained Cable Pull limit Switch
Figure 3: Typical Single Head Switch Installation
Figure 4: Typical Duplex Head Switch Installation
SWITCH MOUNTING, WIRING AND SEALING
Step 1 - Ensure you have the following:
Switch.
l
(2) #10 - 32 UNF screws.
l
#14 - #16 AWG stranded or #16 - #18 AWG solid
l
wire.
Step 2 - Mount switch:
Single head: Mount using (2) #10-32 UNF
l
screws from either front or back of switch.
Ensure a minimum of four threads of
engagement. Torque to 43-52 in.-lb (4.9-5.9 N-
W .
Duplex head: Mount using (2) #10-32 UNF
l
screws through mounting feet on left and right of
switch enclosure. Ensure a minimum of four
threads of engagement. Torque to 43-52 in.-lb
(4,9-5,9 N-m).
For application help: call 1-800-537-6945
Step 3 - Wire switch:
Connect stranded or solid wire to switch's
l
pressure type connector terminals. (Refer to
circuit diagram on switch housing. Diagram
depicts switch contacts when cable is at proper
tension.) Torque terminal screws and ground
screw to 7-9 in.-lb (0,8-1 N-m).
Step 4 - Seal conduit connection:
Seal with Teflon tape or pipe dope. If connector
l
is used to secure cable to enclosure, torque
connector to 16-19 in. lb (1,8-2,2 N-m).
IMPROPER SYSTEM PERFORMANCE
Ensure the attendant circuitry is such that only
l
the momentary interruption of the control circuit
cable pull contacts is required to open and hold
open the control circuit until such time as both
the cable pull switch and the attendant circuitry
are manually reset.
The user is SOLELY RESPONSIBLE for
l
determining the appropriate level of risk
warranting this type of circuitry.
Maintained Cable Pull Limit Switches must be
l
installed in a fashion that complies with all codes
and standards that are applicable to the particular
application of the device.
Failure to comply with these instructions could
l
result in death or serious injury.
ACTUATING CABLE INSTALLATION
Step 1 - Ensure you have the following
3 and 4):
Plastic coated aircraft cable 1/8 in. (3,18 mm) to
l
3/16 in. (4,76 mm) dia. Use a distinctive color,
such as red, to differentiate actuating cable from
other wires or cables in the area.
Thimbles, U-bolt clamps.
l
Cable supports (eyebolts).
Honeywell
MICRO SWITCH Sensing and Control
l
PK 8156 0