In Floor Installation

If the safety mat is embedded into the floor, edge trim is not required. To avoid edge stress, a
gap of about 1.5 mm (0.06 in) must exist between the safety mat and the edge of the flush
fitting. See figure 2-13 below.
IMPROPER USE OF THE FF-SM SERIES SAFETY MAT
• The 30 kg sensitivity of the FF-SM Series safety mats is suitable for the detection of adults
weighing more than 35 kg according to the EN1760-1 European standard.
• Do NOT use FF-SM Series safety mats in public places where children may have to be
detected.
• Use of an additional protective sheet laid on the safety mat (sensor) surface is forbidden
since it may alter the 30 kg sensitivity.
Failure to comply with these instructions will result in death or serious injury.
Figure 2-13 In Floor Installation
Double face adhesive tape can be used to affix the safety mat on the reference floor. The
TESA Ref. 4952 adhesive tape can be used for this purpose.
22 Honeywell • PK 107007-01 EN FR26 GLO 0298 Printed in France
about 1.5 mm (0.06 in)
Floor
FF-SM Series Installation Manual
~1.5 mm