Honeywell SYA14 Series Manual page 671

Safety light curtains
Table of Contents

Advertisement

FF-SRS5924 TROUBLESHOOTING FLOW DIAGRAM
Contacts are
damaged.
No
Ensure maximum
load is within
specifications.
Replace module.
Yes
Check for proper
machine operation
Check for proper
machine operation
8
Yes
Are the outputs
Is the K1/K2
contacts 13/14...33/
LED ON ?
34 closed ?
Yes
Is the problem
resolved?
No
The problem
is external to
the module.
Check for and
correct any
external
causes
(wiring, etc.)
Does manual restart mode
use an external start push
button?
Ensure the "start loop" is closed when the
external start push button is activated (this
tests the correct operation of the push button)
Push and release the external start push
button between S33/S34.
Yes
Is the problem
resolved?
Replace the
safety module.
Machine Down
Yes
Is the "Power" LED
ON
?
No
No
Is the voltage
between A1/A2
present AND within
specifications ?
No
Apply correct voltage AND/
OR check for correct
operation of previously
connected safety device.
No
Ensure that S33/S34 is
jumpered.
Yes
No
107015-10 EN FR26 GLO 1198 Printed in Germany
Yes
Replace the
safety module.