APPLICATION EXAMPLES (continued)
FIG. 12.: DUAL-CHANNEL SAFETY DOOR MONITORING
(WITH CROSS-FAULT MONITORING, AUTOMATIC START MODE)
L1
Fuse
S11
A3
(+)
A4
(-)
N
GENERAL DESCRIPTION OF SAFETY DOOR APPLICATIONS
Protective gates are designed to limit or block access to the moving parts of dangerous machinery. These
gates can be equipped with locking or interlocking devices, usually safety limit switches or any other safety
sensors/switches.
The FF-SRS5988 Emergency Stop module monitors the status of these safety sensor positions. When the
protective gate is open, the initiation of dangerous motion is prevented. When the door is closed again, the
next machine cycle can start, but only after initiating a manual restart sequence.
FUNCTIONAL DESCRIPTION
After opening the door, the two external safety switch contacts S1 and S2 will open (as illustrated above) and
the two internal safety relays K2 and K3 will de-energize. The normally open safety outputs 13/14.. 63/64 will
open relaying the stop condition to the machine control circuitry. After closing the door, S1 and S2 close and
the internal relays K2 and K3 will energize. The six normally open safety contacts will close and an external
manual restart sequence may then be initiated (allowing the machine to operate).
IMPORTANT NOTICES
SAFETY LIMIT SWITCH SEQUENCE
• In order to let the module restart automatically, safety limit switch S1 must not close before switch S2. The
FF-SRS5988 will only restart after the two input channels have been opened and then closed (an
activation).
• In the manual start mode the safety limit switch sequence has no impact.
• In the manual start mode, closing the start push button will immediately close the normally open contacts of
the safety control module and initiate a machine start cycle. The push button must be released before the
next start cycle is allowed. This will prevent automatic start in case the push button is broken in the closed
position.
• The cable resistance between S11/S12 and S21/S23 must be less than 68Ω (ohms) for correct operation
of the safety control module.
• A minimum of 21 vdc must be present between each channel input (S11/S12 and S21/S23) to ensure the
correct detection of sensor(s) outputs status.
107018-04 EN FR26 GLO 1198 Printed in Germany
S33
S34
FF-SRS 5988
Y1 Y2
X1 X2
(B)
Power
Fuses
closed
Sliding guard
(closed position)
open
Honeywell
Machine
Control
9