PROTECTIONS
The test output is not protected against overloads and short circuits. Overloads and short-
circuits may damage this output, however the module will still operate correctly provided the
detection field of the protective equipment is interrupted after power up.
REVERSED POLARITY
This output is protected against reversed polarity, but the module cannot detect a reversed
polarity on the test input of the protective equipment. In such a case, the SSD and OSDs
outputs remain open and the manual restart of the module is impossible. It is recommended
to check correct wiring of the test output by checking the status of the test LED of the
protective equipment. If this connection is made correctly and if no failure is detected, the
SSD output switches ON and the RESTART LED flickers to indicate that manual restart is
necessary (see figure 4.6 Connection of the test output and timing diagram).
Figure 4.7 : Connection of the test output and timing diagram
+24Vdc
ESPE
Test
+
-
29
28
(+)
(-)
TEST
FF-SRM
0V
Features
TEST output
Type
voltage free and without reference potential
Switching capacity
16 mA/24 Vdc
Voltage drop
< 1 Vdc
Protections
galvanic insulation : 500 Vdc, reversed polarity
54
power supply
225 ms
TEST output
OSSDs
SSD
RESTART
LED
the module is
indicator
in test mode
107004-15 EN FR26 ROW 0899 Printed in France
the module
needs to be
restarted