50FY Series
Step 4 - Wire logic amplifier as follows:
• Connect 100 to 128 VAC to logic amplifier
terminals L1 and L2.
• Connect load to logic amplifier relay contact
terminals R1 and R2.
Step 5 - Perform troubleshooting procedure as
required: (see logic amplifier indicators)
IMPROPER SYSTEM PERFORMANCE
If the red ATTENTION INDICATOR LED, located on
the logic amplifier is flashing, DO NOT OPERATE.
Failure to comply with these instructions could
result in death or serious injury.
LOGIC AMPLIFIER INDICATORS
Attention
Indicator
1. If the 50FY Series system appears to be
operational, but the red ATTENTION
INDICATOR LED is flashing, do the following:
• Ensure the sensors are wired to the logic amplifier
correctly.
• Ensure the 22 K Ω resistors are installed in their
proper locations on the logic amplifier.
• Manually actuate sensors and ensure the
corresponding red SWITCH OUTPUT LEDs
above the logic amplifier terminal turn off.
• Ensure sensors and magnet actuators are aligned
and within specified sensing distance.
• Shut amplifier power OFF and wait until the
ATTENTION INDICATOR LED is completely
OFF, then turn the amplifier power ON (power on
reset).
• If the red ATTENTION INDICATOR LED is still
flashing, disconnect the logic amplifier and call the
MICRO SWITCH Application Center (1-800-537-
6945).
4 Honeywell • MICRO SWITCH Sensing and Control
Switch Output
Indicator LEDs
2. If the 50FY Series system is not operating and
the red ATTENTION INDICATOR LED is not
illuminated, do the following:
• Ensure the installed fuses are rated properly and
not blown (0.630A and 1/8A slow blow).
• Ensure the sensors and logic amplifier are wired
correctly.
• Ensure the 22 K Ω resistors are installed in their
proper locations on the logic amplifier.
• Ensure the sensors and magnet actuators are
aligned and within specified sensing distance.
• Remove and restore power (power on reset).
• If the 50FY Series system is still OFF, disconnect
the logic amplifier and return to Honeywell.
Step 6 - Perform functional check as follows:
(see logic amplifier indicators)
1. If the 50FY Series is operating and the red
ATTENTION INDICATOR LED is not illuminated,
do the following:
• If any or all of the sensors are not actuated,
observe the corresponding red SWITCH OUTPUT
LEDs above the logic amplifier terminals for each
sensor are illuminated. Also observe the red
RELAY CONDITION OPEN LEDs are illuminated
(logic amplifier contacts are open).
• Actuate each sensor and observe the
corresponding red SWITCH OUTPUT LED turns
off.
• If all twelve of the red SWITCH OUTPUT LEDs
are off (all sensors are actuated), observe the red
RELAY CONDITION OPEN LEDs are NOT
illuminated. Also observe the green RELAY
CONDITION CLOSED LEDs are illuminated (logic
amplifier contacts are closed).
• If the 50FY Series system performs as indicated
above (step 3), the system is operating correctly.
PK 80391
ISSUE 3