FF-SB Installation Manual

Test Contacts

Test contacts may be used for additional external relay checking. When the link between the
two contacts is open, the light curtain is in the red condition and R2 and R4 (LEDs on receiver)
are illuminated. To return to the green condition, the link between the contacts must be
reestablished.
C4, C5: For FF-SB Original Series or FF-SB CE in factory setting (see figure 3-4).
C4, B3: For FF-SB CE Series in cycle start mode (see figure 3-5).

Factory Settings (receivers only)

Figure 3-4 Replacing FF-SB Original Series with CE Version (factory setting)
For application help: call 1-800-537-6945
RECEIVER
C4
C5
Jumper Link position
on the Receiver
Power Board (factory
setting)
NOTICE: Points C4 and C5 are jumpered
if the optional test function is not used
(no voltage is applied).
Optional test
function
Honeywell • MICRO SWITCH Sensing and Control 49