4. Electrical Connections
4.1 Overview
This chapter contains information about electrical installation and wiring.
IMPROPER INSTALLATION
Strictly adhere to all electrical connection instructions.
Failure to comply with these instructions could result in death or serious injury.
4.2 Connector
Wiring
for
curtains
All FF-SYAqqqqqC2 light curtains have two plastic quick-disconnect connectors.
Emitter units and receiver units use the same connector. The figure below illustrates a
rear view of the connector (crimped contacts inserted this side). Both emitter and receiver
use the same connector type and both connectors use the same type of crimped contacts.
Figure 4-1
View of customer quick-disconnect Connector (Hirschmann N6RFF
connector type)
2
1
3
6
4
5
Rear View of customer Connector
(crimped contacts inserted this side)
Ensure the following tools are available when wiring the quick-disconnect connector:
• A set of wire strippers.
• A flat-head screwdriver.
• A regular crimping tool.
Cross sectional area of the cables: minimum 0.5 mm² / AWG 21, maximum 1.5 mm² /
AWG 16 stranded wire.
Packing Gland and recommended cable diameters to guarantee the IP 65/NEMA 4, 13
sealing: PG11 allows use of cable diameters from 6.5 mm to 10.5 mm (0.25 in. to 0.41 in.)
Install socket contacts into connector as follows:
1.
Strip about 8 mm (0.3 in.) of insulation from the wire end.
2.
Using a crimping tool, crimp the socket contact onto the wire.
107031-23 EN FR26 GLO 1199 Printed in France
FF-SYA qqqqq C2
the
1
2
6
3
5
4
Front View of customer Connector
(Do NOT insert crimped contact from this side)
light
47