FF-SRS5935 TROUBLESHOOTING FLOW DIAGRAM (PAGE 3 OF 3)
Are two channel
inputs selected?
Ensure the S1
switch is in the "with
detection" position.
Disconnect S11. Is input
channel one closed? Also, is
there less than 68 Ohms and more
than 21 Vdc between S11/S12?
Disconnect S21. Is input channel two
closed? Also, is there less than 68
Ohms and more than 21 Vdc
between S21/S22?
107017-11 EN FR26 GLO 0999 Printed in Germany
From
Page 2
No
Yes
cross-fault
Yes to all
questions
No
Reconnect S11
and S21. Correct/
replace the
external sensor(s),
wiring, supply
voltage, etc.
Ensure the S1 switch
is in the "without
cross-fault detection"
position.
Disconnect S11 and
ensure input channel one
is closed, less than 68
Ohms and more than 21
Vdc between
Yes
S11/S12.
Reconnect S11
(and S21).
Safety module has
failed. Replace the
module.
Reconnect S11.
Correct/replace the
external sensor(s),
wiring, supply
voltage, etc.
Go to
Page 2