FF-SPS4 Series Installation Manual
Figure 2-9 Emitter Frequency Selection
Emitter
Check Emission Frequency Setting
Observe the status of both the emitter and receiver emission frequency indicators. The status
of these indicators must be identical. If it is not, make the necessary setting changes. If the
status of the indicators is identical, interrupt the sensing beam of the emitter and observe the
status of the red output indicator on the receiver. The red indicator must be illuminated (see
figures 2-8 and 2-9).
For application help: call 1-800-537-6945
Switch position
Switch
location
OFF
Indicator status :
Frequency F1 (50 kHz)
Light On
Switch position
OFF
Indicator status :
Frequency F1 (40 kHz)
Light Off
Honeywell • MICRO SWITCH Sensing and Control 21