Connections

Perimeter System Wiring

IMPROPER CONTROL SYSTEM
Ensure independent stop circuit relays have mechanically linked contacts that prevent contact
overlapping in the event of a welded contact.
Failure to comply with these instructions could result in death or serious injury.
The following figures illustrate the electrical wiring of the safety perimeter systems . The
customer is responsible for providing the safety relays, R, the restart push-button, the arc
suppressors, and the test circuit. The two NO safety contacts and the NC safety contact of the
FF-SPS4 are designed to switch at a minimum of 50 mA.
Figure 3-5 Wiring Diagram for One Perimeter System
Receiver
A1
A2
2
1
N
O
Mode Selector
Power
A1, A2: One Normally Closed (NC) safety contact
B1, B2 and C1, C2: Two Normally Open (NO) safety contacts
C3, C5: Restart the safety perimeter guarding system and monitor the external relays
34 Honeywell • MICRO SWITCH Sensing and Control
Arc suppressor (see relay
supplier for best value)
R1
Hot
B1
R2
Hot
B2
C1
Additional Output
C2
R1 R2
C3
Restart Pushbutton
C5
C4
R1 R2
Machine
Control
FF-SPS4 Series Installation Manual
Emitter and Receiver
Internal
Neutral
GROUND
(Screw on
connector)
or housing
100 ms < t < 3,4 s
For application help: call 1-800-537-6945