MAXIMUM MUTING SEQUENCE DURATION
The duration of the muting sequence is voluntarily limited to avoid the
permanent mute of the protective equipment. The actuation of the 2 start muting
sensors SMs initiates a timing, and if this timing ends before the information
delivered by the 2 end muting sensors EMs are issued, then the muting sequence is
interrupted and the OSDs outputs of the muting module remains permanently open.
The selection of the appropriate mode of operation sets the maximum duration
of the muting sequence to the values given in chapter 2.4.2 SM inputs .
If this timing is exceeded, press and release the restart push-button to go back
to normal conditions of operation (refer to chapter 2.4.5 Manual restart of the
module).
In the conveyor mode, it may be necessary to press push- buttons P/B1 and
P/B2 to clear the detection field before restarting the module (see chapter 2.4.4
Override function).
2.4.2 SM inputs (start of a muting sequence) (switch ST3)
At least two auxiliary sensors are necessary to start a muting sequence. These two
sensors may be ultrasonic sensors, photoelectric controls, limit switches or inductive
proximity sensors. Correct operation of these sensors is monitored by the muting
module and a muting sequence is allowed if both sensor outputs switch ON within a
time frame set between tmin = 8ms and tmax = programmable from 1s to 8s.
Figure 2.3 : SM inputs timing diagram
t < t
t
< t < t
min
min
SM1
SM1
SM2
SM2
Protection
Protection
(Muting is not
allowed)
∆t = 50 ms
tmin = 8 ms / tmax = programmable from 1 s to 8 s
18
t > t
max
max
SM1
SM2
Protection
Muting
(muting is not
allowed
allowed)