FF-SB Installation Manual
Changing Internal Jumper Link Positions (receiver only)
1. Remove the receiver power supply module from the light curtain housing.
2. Observe and note the position of the jumper links (see Electrical Connections chapter).
3. To replace an original FF-SB Series version light curtain with a FF-SB CE version, no
jumper link change is necessary (see figures 4-16 and 4-17).
4. To reconfigure the factory settings of a new FF-SB Series light curtain to the cycle start
mode, carefully remove the jumper links and plug them in the positions illustrated in figure
4-18.
5. Perform an operational test to ensure proper functional readiness.
Figure 4-16 Factory Setting Jumper Link Positions on Receiver Power Supply Board
Receiver Power
Supply Board
Jumpers
For application help: call 1-800-537-6945
Jumpers
Honeywell • MICRO SWITCH Sensing and Control 73